恒定制热容量运行下变频空气源热泵结霜的系统级建模与能效评估

《Energy》:System-level modeling and energy-performance assessment of frosting in inverter-driven air-source heat pumps under constant-heating-capacity operation

【字体: 大 中 小 】 时间:2026年08月23日 来源:Energy 10.1

编辑推荐:

   AbstractFrost accumulation on the outdoor evaporator of air-source heat pumps (ASHPs) degrades heat transfer, increases air-side pressure

  

AbstractFrost accumulation on the outdoor evaporator of air-source heat pumps (ASHPs) degrades heat transfer, increases air-side pressure drop, and reduces airflow, thereby affecting the complete heat-pump cycle. This study develops a physics-based reduced-order model to investigate the time-dependent frosting response of an inverter-driven ASHP under constant-heating-capacity (CH) operation. The model couples frost growth, evaporator blockage, pressure-drop increase, fan-curve-based airflow reduction, heat-transfer degradation, and heat-pump-cycle behavior. The frosting-related submodels and system-level degradation trends were assessed using published experimental data. The results show that the system-level performance impact of frosting is governed primarily by fan-curve-driven airflow reduction rather than by the direct increase in evaporator thermal resistance. A diagnostic calculation suppressing frost-induced thermal-resistance variation changed the total COP degradation by only 5%, indicating that airflow reduction affects the cycle mainly through the evaporator heat balance and the associated logarithmic mean temperature difference (LMTD). Under CH operation, the ASHP maintains the prescribed heating output as frosting progresses, making the effects of reduced airflow on evaporating temperature, compressor input power, and COP deterioration more pronounced than under fixed-speed-like operation. At the same airflow-ratio termination point, the relative COP reduction in CH mode was approximately 44% greater. Reducing the part-load ratio from 1.00 to 0.80 extended the frosting period by about 1.8 times, although the relative COP loss at the corresponding termination point remained similar. The results provide a system-level interpretation of frosting as an energy penalty during capacity-maintaining operation of inverter-driven ASHPs.IntroductionAir-source heat pumps (ASHPs) are increasingly used as an energy-efficient and low-carbon heating technology because they utilize widely available ambient air without direct fossil-fuel combustion at the point of use. However, their operation is challenged under cold and humid conditions, where the outdoor evaporator surface may fall below both the air dew-point temperature and the freezing point of water, leading to frost formation on the coil. The accumulated frost degrades heat-pump performance and requires periodic defrosting, which interrupts heating continuity and imposes an additional energy penalty. Accordingly, understanding the transient behavior of ASHP systems under frosting conditions remains essential for improving energy efficiency and operational reliability [1], [2].The impact of frost accumulation on ASHP operation arises from coupled thermal and aerodynamic mechanisms. Thermally, the frost layer adds conductive resistance and modifies the air-side convective heat-transfer characteristics of the evaporator by changing the airflow passages and local air velocity. Aerodynamically, the progressive narrowing of the air passages increases the air-side pressure drop; for a fan operating at a fixed speed along its characteristic curve, this shifts the operating point toward a lower airflow rate. Comprehensive reviews have shown that frost accumulation modifies both the thermal and aerodynamic characteristics of forced-air heat exchangers and have emphasized the need to account for evaporator–fan coupling within a dynamic system approach [2], [3]. Accordingly, evaluating ASHP performance under frosting conditions requires a system-level framework that couples the evolving evaporator characteristics and fan-dependent airflow reduction with the thermodynamic response of the complete heat-pump cycle.Early but influential studies established the importance of accounting for frost-induced airflow degradation at the heat-exchanger level. Da Silva et al. [4] developed a physics-based model for fan-supplied tube-fin evaporators and showed that progressive frost clogging and the associated airflow degradation can play a dominant role in evaporator-capacity loss. Ye and Lee [5] further incorporated frost-induced blockage, air-side pressure drop, and fan-curve-based airflow reduction into a numerical model for fin-and-tube heat exchangers used in ASHP applications. Together, these studies provided a strong physical basis for evaluating the coupled thermal and aerodynamic consequences of frosting; however, their analyses remained primarily at the heat-exchanger level.This heat-exchanger-level physical foundation was subsequently extended to examine the effects of frosting on the complete ASHP cycle. Chung et al. [6] developed and experimentally validated a quasi-steady-state numerical model that linked local frost growth, non-uniform airflow distribution, air-side pressure drop, and evaporator heat transfer to ASHP-cycle behavior. The authors showed that system-performance degradation accelerated particularly during the later stages of frosting and that accumulated frost mass alone was insufficient to explain the resulting performance loss. Ma et al. [7] integrated frost formation and melting into a finite-volume evaporator model and presented a comprehensive dynamic ASHP-cycle model that captured non-uniform frost distribution and successive transitions between frosting and reverse-cycle defrosting. Xiong et al. [8] experimentally compared vapor-injection and vapor-bypass ASHP systems under low-temperature frosting–defrosting conditions and evaluated their heating and defrosting characteristics. These studies represent important advances in modeling complete ASHP frosting–defrosting behavior and experimentally evaluating low-temperature ASHP configurations under frosting–defrosting conditions.While these studies advanced the cycle-level understanding of frosting and defrosting, another important issue in modern ASHPs is how variable-speed components are operated during frosting. A separate line of research has examined the deliberate adjustment of compressor and outdoor-fan speeds in variable-speed ASHPs as a means of suppressing frosting. Several map-based studies have shown that different compressor–fan speed combinations can alter the outdoor-coil surface temperature, heating capacity, and frosting tendency [9], [10], [11], [12]. Liang et al. [13] experimentally investigated the effects of different outdoor-airflow levels on system performance and frosting–defrosting losses by varying the airflow rate in a controlled manner. These studies primarily focused on the active coordination of compressor and fan speeds for frost suppression. In contrast, the frost-induced airflow degradation caused by progressive evaporator blockage and the compensatory compressor response required to maintain a prescribed heating capacity represent a different operating condition.Experiments conducted under controlled airflow conditions provide valuable information on frost growth and the evolution of heat-transfer resistance; however, they do not fully reproduce the fan-curve-driven airflow response of a fan-supplied outdoor unit. Badri et al. [3] reported that more than 80% of the studies included in their broad review of the frosting and defrosting literature were conducted under constant-airflow conditions maintained by varying the fan speed. In contrast, Guo et al. [14] experimentally showed that, during the advanced stage of frosting in a split-type ASHP system, both the airflow rate and evaporator-wall temperature decreased rapidly, creating a feedback loop that further accelerated frost growth. More recently, Juhola et al. [15] demonstrated that frost growth substantially increased the air-side pressure drop under constant-airflow conditions, whereas only a limited reduction in heat-exchanger conductance was observed. The authors emphasized that, in an actual system operating with a fixed-speed fan, the increasing pressure drop would reduce the airflow rate. Therefore, representing ASHP operation with a fixed-speed outdoor fan under frosting conditions requires the frost-induced air-side aerodynamic resistance to be explicitly coupled with the fan response.Understanding the coupled response of the evaporator, fan, and heat-pump cycle under frosting conditions is relevant not only to performance prediction, but also to defrost-control studies. Appropriate timing of defrost initiation is important because premature defrosting increases defrost frequency, whereas delayed defrosting causes larger heating-capacity and COP losses. Previous studies have investigated different defrost-initiation indicators, including differential pressure across the outdoor evaporator [16], visual frost coverage [17], model-based volumetric blockage estimation [18], evaporator-outlet superheat [19], evaporating temperature [20], and approach temperature difference [21]. A recent review has also emphasized the role of advanced defrosting techniques, such as vapor injection and thermal energy storage, and highlighted the limited availability of experimental frost-accumulation data under varying operating conditions [22]. In parallel, data-driven and model-based approaches have aimed to adapt defrost control to varying operating conditions [23], [24], including the frosting-rate prediction model developed by Wei et al. [25] for optimizing defrost-control strategies. However, these studies have mainly focused on defrost techniques, defrost timing, and frost-state identification or prediction, rather than on the system-level energy-performance response of capacity-maintaining inverter operation under progressive frosting.Although previous studies have examined fan–heat exchanger interactions, complete ASHP-cycle behavior under frosting conditions, active frost-suppression strategies, and defrost-control-oriented approaches, the time-dependent response of an inverter-driven ASHP remains insufficiently clarified when the system attempts to maintain a prescribed heating capacity under progressively accumulating frost. Under this condition, frost accumulation simultaneously alters evaporator heat-transfer behavior and increases air-side resistance, thereby reducing the outdoor-airflow rate and placing an increasing thermodynamic burden on the heat-pump cycle. A physically interpretable reduced-order framework is therefore needed to couple these thermal, aerodynamic, and cycle-level effects throughout the frosting period. Such a framework can support the systematic evaluation of operating strategy and capacity-level effects under frosting conditions. It may also reveal system-level variables, including the compressor-power-consumption trajectory, that merit further investigation as candidate indicators for defrost initiation.In a previous study, Sezen [26] developed a physics-based logarithmic mean temperature difference (LMTD) model to investigate the effects of evaporator and condenser airflow variations on the operating parameters of inverter-driven ASHPs under frost-free conditions. In that model, airflow rates were prescribed as operating inputs, and their effects on the thermodynamic response of the complete heat-pump cycle were evaluated. The earlier study also identified frost formation on the outdoor evaporator and its effects on airflow and evaporator heat transfer as an important future extension of the airflow-sensitive framework. Building on this framework, the present study extends the analysis to frosting conditions by incorporating the transient growth of frost on the evaporator and its coupled thermal and aerodynamic effects.This study aims to develop a physics-based reduced-order model for investigating the time-dependent effects of progressive frosting on the behavior of an inverter-driven ASHP system. The model couples frost growth with the evolving thermal and aerodynamic characteristics of the evaporator and their effects on airflow rate and heat-pump cycle behavior. The analysis focuses on the practically relevant operating condition in which the inverter-driven system attempts to maintain the required heating capacity as frosting progresses. The developed model is used to evaluate how operating mode and imposed capacity level influence the coupled degradation pathway from frost growth and airflow reduction to the downward shift in refrigerant evaporating temperature, increased compressor input power, and COP deterioration. In particular, the comparison between constant-heating-capacity (CH) operation and fixed-speed-like operation demonstrates how the capacity-maintaining inverter response leads to a distinct time-dependent performance trajectory under frosting conditions. By linking frost-induced aerodynamic degradation to compressor-power demand and COP deterioration, the study frames frosting as a system-level energy-performance problem rather than solely as an evaporator-level heat-transfer issue.Section snippetsSystem description and major assumptionsThe transient performance of an air-source heat pump (ASHP) under frosting conditions was investigated using a time-discretized quasi-steady-state model. The system consists of an inverter-driven compressor, an indoor condenser, an expansion valve, and an outdoor fin-and-tube evaporator. The ASHP was analyzed under constant-heating-capacity (CH) operation. In this operating approach, the prescribed condenser heating capacity is maintained by adjusting the compressor work input within theModel validation and assessmentA direct one-to-one validation of the complete frost-coupled inverter ASHP model is limited by the fact that available frosting experiments generally differ from the present system in terms of heat-exchanger geometry, fan characteristics, compressor control strategy, and reported boundary conditions. Therefore, the model was assessed in a staged manner. First, the frost-accumulation and air-side pressure-drop predictions were assessed using the fan-supplied tube-fin evaporator data of da SilvaResults and discussionThe results are presented by following the physical degradation chain induced by frosting. First, frost accumulation and the resulting geometric blockage are examined. Then, the coupled air-side pressure drop, airflow reduction, and heat-transfer degradation are discussed. Finally, the system-level thermodynamic response under CH mode and the effects of operating strategy are evaluated.The baseline case discussed in Sections 4.1–4.3 was simulated at an outdoor air temperature of , an outdoorConclusionsThis study developed a physics-based reduced-order model to investigate the time-dependent frosting response of an inverter-driven air-source heat pump under capacity-maintaining operation. The model coupled frost growth, evaporator geometric blockage, air-side pressure-drop increase, fan-curve-based airflow reduction, evaporator heat-transfer degradation, and heat-pump-cycle behavior. This framework enabled the progressive degradation pathway from frost accumulation to airflow reduction,Declaration of generative AI and AI-assisted technologies in the manuscript preparation processDuring the preparation of this work, the author used ChatGPT by OpenAI for language editing, academic wording, and manuscript polishing.

摘要 空气源热泵(ASHPs)室外蒸发器上的霜层积聚降低了传热效率,增加了空气侧压降,并减少了风量,从而影响整个热泵循环。本研究开发了一种基于物理的降阶模型,以研究变频驱动 ASHP 在恒定制热量(CH)运行下的时变结霜响应。该模型耦合了霜层生长、蒸发器堵塞、压降增加、基于风机特性曲线的风量减少、传热性能退化以及热泵循环行为。结霜相关子模型和系统级退化趋势利用已发表实验数据进行了评估。结果表明,结霜对系统级性能的影响主要由风机特性曲线驱动的风量减少主导,而非蒸发器热阻的直接增加。一种抑制霜致热阻变化的诊断计算仅使总 COP 退化改变了 5%,表明风量减少主要通过蒸发器热平衡及其相关的对数平均温差(LMTD)影响循环。在 CH 运行下,随着结霜进展,ASHP 维持规定的加热输出,使得风量减少对蒸发温度、压缩机输入功率和 COP 恶化的影响比在类似定速运行下更为显著。在相同的风量比终止点,CH 模式下的相对 COP 减少量大约高出 44%。将部分负荷率从 1.00 降低到 0.80 使结霜期延长了约 1.8 倍,尽管在相应终止点的相对 COP 损失保持相似。结果为变频驱动 ASHP 在容量维持运行期间将结霜视为一种能量惩罚提供了系统级解释。

引言 空气源热泵(ASHPs)越来越多地被用作一种节能且低碳的供暖技术,因为它们利用广泛可用的环境空气,且在使用点不进行直接化石燃料燃烧。然而,在寒冷潮湿条件下,其运行面临挑战,此时室外蒸发器表面可能低于空气露点温度和水的冰点,导致盘管上结霜。积聚的霜层降低热泵性能,需要定期除霜,这中断了供暖连续性并施加了额外的能量惩罚。因此,了解 ASHP 系统在结霜条件下的瞬态行为对于提高能效和运行可靠性仍然至关重要 [1], [2]。

霜层积聚对 ASHP 运行的影响源于耦合的热力学和空气动力学机制。从热力学角度看,霜层增加了导热阻力并改变了空气侧对流换热特性,通过改变气流通道和局部空气速度。从空气动力学角度看,空气通道的逐渐变窄增加了空气侧压降;对于沿其特性曲线以固定速度运行的风机,这将工作点移向较低的风量。综合综述表明,霜层积聚改变了强制通风换热器的热力学和空气动力学特性,并强调需要在动态系统方法中考虑蒸发器 - 风机耦合 [2], [3]。因此,评估结霜条件下的 ASHP 性能需要一个系统级框架,将不断演变的蒸发器特性和依赖风机的风量减少与完整热泵循环的热力学响应耦合起来。

早期但具有影响力的研究确立了在换热器层面上考虑霜致风量退化的重要性。Da Silva 等人 [4] 为风机供风格式蒸发器开发了一种基于物理的模型,并表明渐进的霜堵塞和相关的风量退化可能在蒸发器容量损失中起主导作用。Ye 和 Lee [5] 进一步将霜致堵塞、空气侧压降和基于风机特性曲线的风量减少纳入用于 ASHP 应用的翅片管换热器的数值模型中。这些研究共同为评估结霜的耦合热力学和空气动力学后果提供了强有力的物理基础;然而,它们的分析主要停留在换热器层面。

这种换热器层面的物理基础随后被扩展以检查结霜对完整 ASHP 循环的影响。Chung 等人 [6] 开发并实验验证了一种准稳态数值模型,将局部霜层生长、不均匀气流分布、空气侧压降和蒸发器传热与 ASHP 循环行为联系起来。作者表明,系统性能退化在结霜后期阶段尤为加速,且仅累积的霜质量不足以解释由此产生的性能损失。Ma 等人 [7] 将霜的形成和融化整合到有限体积蒸发器模型中,并提出了一种全面的动态 ASHP 循环模型,捕捉了不均匀的霜分布以及结霜和逆循环除霜之间的连续转换。Xiong 等人 [8] 实验比较了低温结霜 - 除霜条件下的蒸气喷射和蒸气旁通 ASHP 系统,并评估了它们的加热和除霜特性。这些研究代表了在建模完整 ASHP 结霜 - 除霜行为和实验评估结霜 - 除霜条件下低温 ASHP 配置方面的重要进展。

虽然这些研究推进了对结霜和除霜的循环级理解,但现代 ASHPs 中的另一个重要问题是可变速度组件在结霜期间如何运行。另一系列研究考察了在变速 ASHPs 中故意调整压缩机和室外风机转速作为抑制结霜的手段。几项基于映射的研究表明,不同的压缩机 - 风机转速组合可以改变室外盘管表面温度、制热量和结霜倾向 [9], [10], [11], [12]。Liang 等人 [13] 通过在受控方式下改变风量,实验研究了不同室外空气流量水平对系统性能和结霜 - 除霜损失的影响。这些研究主要集中在压缩机和风机转速的主动协调以抑制霜层。相比之下,由渐进蒸发器堵塞引起的霜致风量退化和为维持规定制热量所需的补偿性压缩机响应代表了不同的运行条件。

在控制空气流量条件下进行的实验提供了关于霜层生长和传热阻力演变的有价值信息;然而,它们不能完全重现风机供式室外单元的风机特性曲线驱动的风量响应。Badri 等人 [3] 报告说,在他们广泛的结霜和除霜文献综述中,超过 80% 的研究是在通过改变风机转速保持恒定空气流量条件下进行的。相比之下,Guo 等人 [14] 实验表明,在分体式 ASHP 系统的结霜晚期阶段,风量和蒸发器壁温都迅速下降,形成了一个进一步加速霜层生长的反馈循环。最近,Juhola 等人 [15] 证明,在恒定空气流量条件下,霜层生长显著增加了空气侧压降,而仅观察到换热器导热的有限减少。作者强调,在实际系统中,使用固定速度风机运行时,增加的压降将减少风量。因此,表示结霜条件下使用固定速度室外风机的 ASHP 运行需要显式地将霜致空气侧空气动力学阻力与风机响应耦合起来。

了解结霜条件下蒸发器、风机和热泵循环的耦合响应不仅与性能预测相关,也与除霜控制研究相关。合适的除霜启动时机很重要,因为过早除霜会增加除霜频率,而延迟除霜会导致更大的制热量和 COP 损失。以前的研究调查了不同的除霜启动指标,包括室外蒸发器上的压差 [16]、视觉霜覆盖 [17]、基于模型的体积堵塞估计 [18]、蒸发器出口过热度 [19]、蒸发温度 [20] 和趋近温差 [21]。最近的一次综述也强调了先进除霜技术的作用,如蒸气喷射和热能储存,并突出了在不同运行条件下实验霜层积累数据可用性有限 [22]。与此同时,数据驱动和基于模型的方法旨在使除霜控制适应不同的运行条件 [23], [24],包括 Wei 等人 [25] 为优化除霜控制策略开发的结霜率预测模型。然而,这些研究主要集中在除霜技术、除霜时机和霜态识别或预测上,而不是在逐步结霜下容量维持变频运行的系统级能量性能响应上。

尽管以前的研究考察了风机 - 换热器相互作用、结霜条件下的完整 ASHP 循环行为、主动防霜策略和面向除霜控制的方法,但当系统试图在逐渐积聚的霜层下维持规定的制热量时,变频驱动 ASHP 的时变响应仍未得到充分阐明。在这种条件下,霜层积聚同时改变了蒸发器传热行为并增加了空气侧阻力,从而减少了室外空气流量,并对热泵循环施加了不断增加的热力学负担。因此,需要一个物理上可解释的降阶框架,以在整个结霜期内耦合这些热力学、空气动力学和循环级效应。这样的框架可以支持在结霜条件下对运行策略和容量级效应的系统评估。它还可能揭示系统级变量,包括压缩机功耗轨迹,值得进一步研究作为除霜启动的候选指标。

在先前的研究中,Sezen [26] 开发了一种基于物理的对数平均温差(LMTD)模型,以研究在无瑕霜条件下蒸发器和冷凝器空气流量变化对变频驱动 ASHPs 运行参数的影响。在该模型中,空气流量被指定为运行输入,并评估了其对完整热泵循环热力学响应的影响。较早的研究还确定了室外蒸发器上的霜层形成及其对空气流量和蒸发器传热的影响作为空气流量敏感框架的一个重要未来扩展。在此基础上,本研究通过将蒸发器上霜层的瞬态生长及其耦合的热力学和空气动力学效应纳入分析,将分析扩展到结霜条件。

本研究旨在开发一种基于物理的降阶模型,以研究逐步结霜对变频驱动 ASHP 系统行为的时变效应。该模型将霜层生长与蒸发器不断演变的热力学和空气动力学特性及其对风量和热泵循环行为的影响耦合起来。分析专注于实际相关的运行条件,即变频驱动系统试图随着结霜进展维持所需的制热量。开发的模型用于评估运行模式和施加的容量水平如何影响从霜层生长和风量减少到制冷剂蒸发温度下降、压缩机输入功率增加和 COP 恶化的耦合退化路径。特别是,恒定制热量(CH)运行与类似定速运行之间的比较展示了容量维持变频响应如何在结霜条件下导致独特的时变性能轨迹。通过将霜致空气动力学退化与压缩机功率需求和 COP 恶化联系起来,本研究将结霜框定为系统级能量性能问题,而不仅仅是蒸发器级传热问题。

章节片段

系统描述和主要假设
空气源热泵(ASHP)在结霜条件下的瞬态性能是使用时间离散化准稳态模型进行调查的。系统由变频驱动压缩机、室内冷凝器、膨胀阀和室外翅片管蒸发器组成。ASHP 在恒定制热量(CH)运行下进行了分析。在这种运行方法中,通过调整压缩机功输入来维持规定的冷凝器制热量,在

模型验证与评估
对完整霜耦合变频 ASHP 模型进行直接的一一对应验证受到限制,因为可用的结霜实验通常在换热器几何形状、风机特性、压缩机控制策略和报告的边界条件方面与当前系统不同。因此,该模型以分阶段的方式进行了评估。首先,使用 da Silva 的风机供风格式蒸发器数据评估了霜积聚和空气侧压降预测

结果与讨论
结果按照结霜引起的物理退化链呈现。首先,检查霜层积聚及其导致的几何堵塞。然后,讨论耦合的空气侧压降、风量减少和传热退化。最后,评估 CH 模式下的系统级热力学响应和运行策略的影响。

第 4.1–4.3 节讨论的基准案例是在室外空气温度为 ,室外...下模拟的

结论
本研究开发了一种基于物理的降阶模型,以研究容量维持运行下变频驱动空气源热泵的时变结霜响应。该模型耦合了霜层生长、蒸发器几何堵塞、空气侧压降增加、基于风机特性曲线的风量减少、蒸发器传热退化以及热泵循环行为。该框架实现了从霜层积聚到风量减少的渐进式退化路径,

稿件准备过程中生成式人工智能和人工智能辅助技术的声明
在本工作的准备过程中,作者使用了 OpenAI 的 ChatGPT 进行语言编辑、学术措辞和稿件润色。

使用本工具后,作者根据需要审阅并编辑了内容,并对已发布文章的内容承担全部责任。
利益冲突声明
作者声明,他没有已知的竞争性经济利益或可能影响本文报告工作的个人关系。
数据可用性声明
应要求提供数据。
资助
本研究未从公共、商业或非营利部门的资助机构获得任何特定拨款。
利益冲突声明
? 作者声明,他们没有已知的竞争性经济利益或可能影响本文报告工作的个人关系。
库特拜·塞森
ALTSO 高等教育职业院校,阿拉尼亚阿拉丁凯库巴特大学,07425 阿拉尼亚,安塔利亚,土耳其